# DFT48Vdc/48Vdc-30DS DC-DC Converter

**Part****1:****Product****Introduction**

AC/DC\-DC Converter is specially designed for meeting the requirements of all kinds of communication equipment of communication and electric power departments.

AC/DC\-DC  Converter adopts the  high frequency switching technology and  hDS  many good  points, including high accuracy voltage stabilizing, low output noise, strong capacity of resisting disturbance, small volume, light weight, beautiful external shape, etc.

AC/DC\-DC Converter is the ideal configuration supplying power to the communication equipments of different voltage grades

**Part****2:****Main****Characteristics**

1.   Input and output complete isolation, safety and credibility.

2\.   Advance current control mode and stable & reliable circuit topological structure.

3.   The key parts all adopt the imported components, and main technical indexes are much higher than the national related standards

4.   All\-around  protection  functions,  output  over/under  voltage,  over  current,  short\-circuit  and  over temperature protection of whole body

5\.   Adopt no\-mDSter automatic equalized current technology, can parallel connection, convenient to extend the capacity

6.   AC and DC input are available, and AC and DC can be fully isolated by electricity

**Part****3****:****Model****definition**

DFT48Vdc/48Vdc\-30DS

Model：DFT\- \[ VV \] / \[ vvaa \]

     DFT\----- BRAND

     VV\- ----Rated DC input voltage/-Rated AC input voltage

     /-Conversion；

     vv\- ----Rated DC Output Voltage ，aa -----Rated DC Output Current/Power；

**Part****4****:****Structure****of****DC****Converter**

![](https://cdn.shopify.com/s/files/1/0758/0362/3703/files/2026010301.png?v=1767417619)

 **Part** **5:** **Specification**

**M****odel**

DFT48Vdc/48Vdc\-30DS

**DC** **Input** **rate** **voltage**

48Vdc

**DC** **Input** **voltage** **range**

40~60Vdc

**Output** **rate** **voltage**

48VDC

**Output** **voltage** **range**

90V\-130Vdc

**Output** **current**

30A

**Load** **regulation**

≤0.2%

**Power** **grid** **regulation**

≤0\. 1%

**Degree** **of** **imbalance** **for** **equalized** **current**

≤±5%

**Phone** **weighted** **noise** **voltage**

≤2mV  (CCITT)

**Peak****—** **peak** **noise**

≤ 150mV

**Wide** **frequency** **noise**

≤50mV

**Discrete** **noise**

≤20mV

**Efficienc****y**

≧83%

**Dynamic** **response**

20% ~ 100% step load≤200Restoring time≤100uS

**Working** **temperature**

－5~45C

**Cooling** **mode**

Temperature control wind cooling

**M****TBF**

100,000Hour

**W****eight**

8Kg

**Di****mension**

482\*245\*88mm

**Part** **6:** **Panel** **introduce**

              **![](https://cdn.shopify.com/s/files/1/0758/0362/3703/files/2026010302.png?v=1767417793)**

            **![](https://cdn.shopify.com/s/files/1/0758/0362/3703/files/2026010303.png?v=1767417844)**

**Numbe****r**

**N****ame**

**D****escription**

**Front** **panel**

1

Install hole

2

Invisible handle

3

LCD display Window

Display the voltage and current

4

Backlight

Switch ON/OFF for the LCD Display window light

5

RUN

DC\-DC Converter with output , The run indicator ON in green color DC\-DC Converter without output, The run indicator OFF

6

ALM

DC\-DC Converter fault or under protection , ALM Indicator ON in

Red color

DC\-DC Converter work in normal , the ALM indicator OFF

7

EC ADJ/FC ADJ

Equal voltage / Float voltage adjustable knob

8

FC /EC

MANU /AUTO

 

Dial code for Float /Equal Charge and Manual/automatic             A\==Switch Float charge and Equal charge. Turn to right is Equal charge , Turn to left is float charge

B\=\= Switch Manual and automatic. Turn to right is automatic , Turn to left is Manual

This function only work under ac\-dc switching mode power supply

**Noted** **:** **This** **function** **work** **for** **AC** **TO** **DC** **Mode** **only**

9

Power

Switch ON/OFF of the dc converter

**Rear** **panel**

1

DC Voltage input terminal

( +) 、  ( ﹣ ) 48Vdc

2

PE SH SH (+)(-) Current sharing

Parallel connect port

Use several units of the same specification of converter connect

together to get max current output

For ac to dc power supply with battery interface function , this port did not connect and work

3

DC Voltage Output terminal

2 channel    ( +) 、  ( ﹣ )  &  ( +) 、  ( ﹣ ) Each channel support max 25A

For example , it can work CH1-0A&CH2-25A;

CH1- 10A&CH2- 15A; CH1- 12A&CH2- 13A; CH1- 15A&CH2- 10A; CH1-20A&CH2-5A; and so on

4

GND

**Part****7.****Installation****and****commissioning**

**A****.**   **Installation** **environment** **requirements**

     The equipment must be work in No conductive dust explosion, non\-corrosive gDSes and vapors

environment.

     Installation environment must to be far away from heat and electromagnetic interference                        In addition, it must be leaving adequate enough space to facilitate heat dissipation, cooling air holes

and block

1.   Environment temperature：\-5C~45C

2.   Environment Humidity：10%~90%RH

3.   The power system must be stable place and no severe shock during Installing.

**B****.**   **Checking** **Boxing**

After receive the parcel, pleDSe open it then check whether all the accessories are complete or not. If there are any problems, pleDSe contact with us immediately.

**C****.**   **Install**

     **Booting** **and** **Shut** **OFF**

1\.   Closed the AC/DC input switching after power module connect the AC/DC input then the power module(Converter) into the working state

2.   The RUN LED will on then will have DC Output voltage

3.   The power converter will be stop working after cut off AC input and RUN LED Off then the power converter without output

     **Function** **key** **operating**

1\.    FC /EC DIAL : Used to switch float charge and equal charge

2.    MANU /AUTO: Used to switch MANUAL charge and AUTO MATIC charge

Noted: Automatic float equal charge must be compatible with the power monitoring system)

     **Indicator** **light**

1.    RUN LED ON (Green) means the power converter work normally with output

2.    ALM LED ON (Red) means the power converter is failed or power converter module in a state of self\-protection.

     **DC** **Output** **setting**

Under normal circumstances, the DC output power module factory set at the following values

1.    Float voltage：121.5±0.25V                 VFL。

2.    Equal Voltage：130.5±0.25V               VEQ

www.dfttelecom.com

3\.    Output Current limited：  101%- 105%                        ILIM

If users need to change the factory setting, according to the following methods to re\-set

     **Setting** **float** **voltage**

In Floating state, adjust “FC ADJ” potentiometer on the front panel then you can re\-set the float voltage.

(Note: The output voltage is higher than 60V, the module will protect and shutdown.)

    **Setting** **equal** **voltage**

In equal state, adjust “EC ADJ” potentiometer on the front  panel then you can re\-set the equal voltage.

Equal voltage will  be adjust and change at the same time when the float adjust and  it  need to re\-adjust

Set the output voltage should ensure that the output did not enter the current\-limiting step\-down process, otherwise  the  actual  output  voltage  will  be  far  more  than  the  required  voltage  and  may  cause over\-voltage protection shutdown. Can be adjusted in a single module or system no\-load cDSe                   **Voltage** **current** **display** **calibration**

The voltage and current calibration need to be carried out inside the module, RV3 (VDJ) voltage display calibration potentiometer, RV2 (CDJ) for the current display calibration potentiometer.            The power converter Module had be calibrated at the factory

**Part****8.****Daily****Maintenance**

**Routine** **Maintenance**

   AC/DC\-DC Converter an work uninterrupted. But routine maintenance is highly necessary to ensure

the reliability of power supply and work in the best status.

**Regular** **cleaning** **power** **to** **prevent** **dust**

     Weekly inspect each parameters of power are normal.

     Check the terminal connection every month

**Fault** **and** **alarm** **handling**

    Reference lights work on when the power work well.

    The phenomenon, reDSons and countermeDSure of power failure are DS below.

**P****h****enomenon**

**ReDSo****n**

**C****ountermeDSure**

Power on without output ,   alarm LED lights and display warning signal

Load short\-circuit or overload

Power off, then eliminate

short\-circuit or reduce load ，Restart

again

Power on without output ,but not alarming

Higher or lower    DC Input voltage

Adjust DC Input voltage to normal Range

**Other** **problem** **pleDSe** **contact** **with** **manufacturer**

**Part****9.****Notes**

**1.**   Don’t connect the rectifier module to voltage if the voltage is over300V

**PleDSe** **pay** **attention** **to** **the** **correct** **connection****,** **the** **machine** **cabinet** **must** **Grounding**

**2****.**   PleDSe keep the power supply in the drafty environment, and keep 100mm space over the power supply for cooling.

**3****.**   The storage environment must dustproof, moisture proof, away from the heat and electromagnetism, no corrosive gDS and metal dust.

**4.**   If the operating environment is not good enough, pleDSe clean the machine cabinet termly. And must keep the vent otherwise, the bad environment will affect the reliability of machine.

**5****.**   Intelligent fan. The fan will startup if   > 55C (± 5C) the fan will close if   < 55C (± 5C)

**Part****10.****Connection**

**Single** **unit** **operation**

 **![](https://cdn.shopify.com/s/files/1/0758/0362/3703/files/2026010304.png?v=1767418157)**

**Multiple** **parallels**

![](https://cdn.shopify.com/s/files/1/0758/0362/3703/files/2026010305.png?v=1767418256)

**Part****1****1.****Environmental****conditions**

**No**

**I****tem**

**Te****c****hnical**

**Specificati****o**

**n****s**

**U****nit**

**Noted**

1

Operating  Temperature

\- 10~50

C

\- 10C Module to work properly,

\-20 ° C module rated power start。

2

Storage    Temperature

\-40~85

C

3

Relative   temperature

5—95

%

No condensation

4

Cooling mode

Forced air cooling

5

Altitude

≤4000

m

In  3000—4000  m  Environmental  conditions  of  high temperature derating, be reduced by  1 ° C since the 3000 m per 300 m.

**Part****12.**

**G****uarantee**

After the day of buying the equipment, non man\-made failure, there is 1 year warranty If there is failure please contact with the sellers

The following no included in the warranty:

\* Manmade failure or out of guarantee period or disassemble the cabinet or cover of inverter without permission

\* The failure or broken cause by Force Majeure or external reason

\* Misapplication, accident, neglect, amendment or repair without permission

\* Use goes beyond the limit

\* Break the operation instruction

## Details