Plug-in DC power system DFT00105
Plug-in DC power system DFT00105
Не удалось загрузить сведения о доступности самовывоза
1.1 System Introduction
The product consists of AC power distribution unit, DC power distribution unit, rectifier unit, monitoring unit, etc. It can be embedded in the cabinet to provide stable 48V DC power supply for communication equipment.

1.2 System Features
.The rectifier module uses full soft switching technology.
.The rectifier module uses non-damage-free hot-swap technology, plug and play, easy to maintain.
. Meet the requirements of energy-saving grading standards for switching power supply equipment for communications.
. Perfect battery management. It can realize automatic floating charge conversion, has battery over-discharge protection function, and can realize temperature compensation, automatic voltage regulation, stepless current limiting, battery capacity calculation, online battery testing and other functions.
. Features high power and high density.
. Support SNMP, Http, Https, and other protocols.
. Support support English, Chinese, Russian and other languages.
.Systems with different configurations can be customized according to your needs.
1.3 System configuration table
|
Rectifier module |
48VDC50A*1PCS |
|
|
AC power distribution unit |
input |
40A/1PN*1 |
|
Output |
/ |
|
|
DC distribution unit |
Load output |
LLVD:63A/1P*1+32A/1P*2 |
|
/ |
||
|
Battery connector |
100A/1P*1 |
|
|
SPD |
/ |
|
2.system parameter
2.1Environmental parameters
|
Item |
Configuration |
|
Operating temperature |
–10℃~+75℃ |
|
Storage temperature |
–40℃~+75℃ |
|
Relative humidity |
5%~95%(no condensation) |
|
Altitude |
≤4000m(When the altitude ranges from 3000 m to 4000 m, the operating temperature decreases by 1ºC for each additional 200 m) |
2.2 Technical Parameters
|
Parameter type |
Parameter name |
description |
|
AC input |
Input Voltage Range |
85VAC~300VAC |
|
Rated Input Voltage |
110VAC / 220VAC |
|
|
Frequency |
45Hz~ 66Hz, rated at 50Hz/60Hz |
|
|
Factor |
≥ 0.99 |
|
|
DC output |
Voltage regulation accuracy |
≤±0.6% |
|
Output voltage range |
42V DC~58V DC |
|
|
Default output voltage |
53.5V DC |
|
|
Maximum output power |
50A |
|
|
Peak-to-peak murmur voltage |
≤200mV(0~20MHz) |
|
|
System efficiency |
≥95% |
|
|
pressure drop |
≤500mV |
|
|
ACinput protection |
Input over voltage protection |
290Vac<Input voltage<300Vac:The warning light is on,the output is normal 300Vac<Input voltage:output off |
|
Input over-voltage recovery |
Input voltage<290Vac,automatic recovery |
|
|
Input under-voltage protection |
Input voltage<80±5Vac output off |
|
|
Input under-voltage recovery |
Input voltage>80~90VAC, automatic recovery |
|
|
Output over-voltage protection |
58.5VDC~60.5VDC, locks out, over-voltages can be recovered by re-powering on |
|
|
Output short-circuit protection |
It can be short-circuited for a long time, and it can be automatically restored after the short-circuit disappears. |
|
|
Over temperature protection |
With over temperature protection >Automatic recovery at 55°C |
|
2.3Battery Management Functions
|
Management type |
condition |
|
Battery low voltage |
The output voltage is lower than the set low battery voltage value (factory default 46V), and the system emits an audible and visual alarm. |
|
LLVD |
When the battery voltage drops to DC46V, the monitoring module controls the contactor action, shutting down the non-critical loads and retaining the critical loads to ensure that the critical loads do not power down. |
|
BLVD |
The system can set the cut-off protection value according to the battery parameters (factory default 43.2V), cut off all loads according to the battery discharge voltage, and after the mains power returns to normal, the system voltage will automatically recover after reaching the set value. |
|
Battery flush charge management |
1、 When the battery charging current is greater than the set maximum charging current, the system charges the battery at a constant current; 2、 When the constant current is charged to the average charging voltage, the system performs a constant voltage equal charge; 3、 When the constant voltage average charge flow is small enough to be below the average charge to float charge flow, the battery is floated; 4、 When the float charge current is greater than the float charge to the average charge flow, the system is evenly charged; 5、 Floating charge continuous time to the set time is automatically converted to equal charge, 6、 The constant pressure equalization time exceeds the set average charging duration, and the floating charge is automatically transferred; 7、 It can also be manually converted to a floating charge. |
|
Temperature compensation |
With the change of battery ambient temperature, the float charge voltage of the system can be automatically adjusted by 52mV/group/°C (which can be set according to the battery parameters), the higher the battery temperature, the lower the float charge voltage, the lower the battery temperature, and the higher the float charge voltage. |
|
Battery SOC |
After accurately setting the battery capacity and remaining capacity value, the monitoring module adjusts the charging and discharging modes of the battery according to the data set by the user, and implements some protection measures (charging current limitation, charging voltage temperature compensation, etc.) to dynamically adjust the remaining capacity value. |
2.4 Safety/EMC/Surge Protection
|
NO. |
Item |
standard |
Remarks |
|
|
1 |
electrical strength |
Input—Output |
3000Vac/30mA/1min |
For power distribution frames only, no flying arcs, no breakdowns |
|
Input—Earth |
1500Vac/30mA/1min |
|||
|
Output—Earth |
500Vac/30mA/1min |
|||
|
2 |
Insulation resistances |
Input—Output |
≥2MΩ@500Vdc |
|
|
Input—Earth |
≥2MΩ@500Vdc |
|||
|
Output—Earth |
≥2MΩ@500Vdc |
|||
|
3 |
contact current |
Input—Earth |
≤3.5mA |
|
|
4 |
earth resistance |
<0.1Ω@40A/2min |
|
|
|
5 |
electric electromagnetic eclectic capacitive capacitive Requirements Requirements |
conductive interference(CE) |
CLASSA |
EN55022 |
|
radiation interference(RE) |
CLASS A |
EN55022 |
||
|
electrostatic immunity (ESD) |
Parts of the shell that can be touched by hand during normal operation. 1、Contact discharge ± 6KV; air discharge ± 8KV Judgement B (test on the power); 2、Contact discharge ±8KV; air discharge ±10KV judgement R (test without power); Conductor inside the signal interface: contact discharge ±2KV criterion R; (power on during the test, the address line and the equalisation line are not tested); |
IEC61000-4-2 |
||
|
radiation immunity(RS) |
LEVEL 3 A |
IEC61000-4-3 |
||
|
conducted immunity(CS) |
LEVEL 3 A |
IEC61000-4-6 |
||
|
Fast Transient Pulse Swarm(EFT) |
LEVEL 3 B |
IEC61000-4-4 |
||
|
surge |
LEVEL 4 B |
IEC61000-4-5 |
||
|
current harmonic |
CLASS A |
IEC61000-3-2 |
||
2.5mechanical property
|
unit |
Parameter name |
errors |
Note |
|
high |
1U |
/ |
|
|
width |
482.6mm |
/ |
|
|
depth |
380mm |
/ |
Not Includes terminals |